lasted nearly 5 years in tenanted property before E5 error

Click here if this is your business
Remeha Avanta Plus
★★☆☆☆
2.0
26.0% of users recommend this

Milian's review of Remeha Avanta Plus

“lasted nearly 5 years in tenanted property before E5 error”

★★☆☆☆

written by Milian on 28/03/2015

I was advised to buy this combi boiler nearly 5 years ago , alternative was Valliant. It is a powerful efficient boiler- had a new bathroom installed and the bathroom installer said it was producing too much hot water!, -produces good hot water . After 4 years and 10 months tenants are getting E5 error message. Intermittent fault. Called Rehema re 5 year warranty and they say its only for parts£300+ charge for call out to fit E5 kit. Rehema (was Broag) have now been taken over by Baxi , who are still selling the same boiler under Baxi name , so its not discontinued. Wish I had chosen Valliant. Not sure if E5 kit will fix problem.

  • Value For Money

If you are commenting on behalf of the company that has been reviewed, please consider upgrading to Official Business Response for higher impact replies.

Chestnut2000's Response to Milian's Review

Written on: 25/10/2016

The E5 Error was a failure of the ignition module on my Avanta 39C. The same module passes the ionisation current to the controller.

The part was around £30 and it's a plug in part fitted within 5 minutes. People assume that because the boiler fires up that the ignition module is not at fault.

Another cause can be the main burner gasket that was originally a fireproof rope, It has been redesigned as a graphite gasket. Regular servicing should eliminate the burner gasket issue as they form part of the service kit.