Had this fitted to a rental property. It has given a non stop supply of E4/E5 errors just like all the other bad reviews. I've had so many parts replaced there's too many to mention.
AVOID like the plague!!!
As rated by our community of reviewers
Chestnut2000's Comment
Written on: 25/10/2016
The E5 Error was a failure of the ignition module on my Avanta 39C. The same module passes the ionisation current to the controller.
The part was around £30 and it's a plug in part fitted within 5 minutes. People assume that because the boiler fires up that the ignition module is not at fault.
Another cause can be the main burner gasket that was originally a fireproof rope, It has been redesigned as a graphite gasket. Regular servicing should eliminate the burner gasket issue as they form part of the service kit.